Norcold N641 / N841 / N1095 L1 oP Code (High Temperature Limit Switch Open)
L1 oP CODE
Norcold N641 / N841 / N1095 L1 oP Code (High Temperature Limit Switch Open)
The display alternates between L1 and oP (often written LI OP) and the alarm beeps. The high temperature limit switch on the cooling unit is open or disconnected. It opens when the cooling unit gets too hot, to protect against overheating and fire. Don’t reset it yourself. Work through every check below first. The reset comes last, and we recommend a certified RV technician do it.
Before you start
- Level first. Make sure the RV is parked level. Running off-level is a common cause of overheating on absorption fridges.
- Don’t reset it first. Resetting the switch without finding the cause is a fire risk. It’s the last step, and we recommend a certified RV technician do it. The Norcold limit switch for these models is discontinued, so it can’t be replaced.
- Where it is. Clamped to the cooling unit, behind the lower outside vent. Its two wires run to LIMIT IN and LIMIT OUT on the power board.
- No switch? Not every model has one. Some N641, N841 and N1095 models have only a jumper wire across LIMIT IN and LIMIT OUT on the power board. If the power board was replaced and that jumper wasn’t moved to the new board, that alone causes this code. Step 1 covers it.
Fits these models
Includes the 2-way and 3-way versions, plus the .3 and IM (ice maker) versions.
STEP 1
Check LIMIT IN and LIMIT OUT
Take the cover off the power board and look at the LIMIT IN and LIMIT OUT terminals. Some N641, N841 and N1095 models have a thermal switch wired there. Some don’t have a thermal switch at all, just a short jumper wire across the two terminals. If yours has a jumper, make sure it’s tight on both ends.
Are LIMIT IN and LIMIT OUT empty, with no switch wires and no jumper?
Install the jumper
Your fridge has no thermal switch, so the board needs a jumper across LIMIT IN and LIMIT OUT. This is the usual cause after a power board replacement: the jumper on the old board wasn’t moved to the new one. Move the jumper from the old board (or install a new one), then turn the fridge off and back on. The code should clear.
STEP 2
Rule out AC ripple
Dirty power from the converter can trip this code even when nothing is overheating. Set your meter to AC volts and measure across the fridge’s 12V DC supply while plugged into shore power. See how to check for AC ripple.
Is there more than 0.3 volts AC on the 12V DC supply?
Fix the converter first
The converter isn’t filtering its output, and the ripple can cause this code. Replace or repair the converter before you replace any fridge parts, then turn the fridge off and back on. If the code is still there, go to Step 3. Read AC Ripple: The Silent Killer of RV Refrigerator Power Boards.
STEP 3
Think back
Before L1 oP showed up, was the fridge cooling normally?
Was the fridge cooling before the code appeared?
Suspect the cooling unit
If it wasn’t cooling well before the code, the cooling unit is likely failing. See what causes cooling unit failures, then go to Step 9 to check it for leaks.
STEP 4
Look at the burner area
Check the burner and flue area for signs of overheating (blue).
Did the burner overheat (blue)?
No burner overheating
No sign of burner overheating. Skip to Step 6 to check the airflow.
STEP 5
Check for insulation in the way
Look at the heat deflector cap on top of the flue and at the burner box.
Is the heat deflector cap or burner box blocked with insulation?
Clear the insulation
Pull the insulation away from the deflector cap and burner box. Then finish with Steps 9 and 10: check the cooling unit for leaks and have a technician reset the switch.
NOT THE BURNER
Check the airflow and the fans that move it.
STEP 6
Check the airflow
Look at the roof or side vent and the lower vent, and the space behind the fridge. Anything blocking air from moving through the enclosure counts: leaves, nests, stored items, loose insulation.
Is something blocking airflow through the enclosure?
Clear the obstructions
Clear everything out of the vent path. See why venting matters. Then finish with Steps 9 and 10: check the cooling unit for leaks and have a technician reset the switch.
STEP 7
Check the fans
With the fridge running, check that the cooling fans behind the fridge spin when the back gets hot. Not all N641, N841 and N1095 models have cooling fans. If yours has none, skip Steps 7 and 8 and go straight to Step 9.
Are the fans okay?
Replace the fans
Replace the cooling fans. Ask a tech to match the right fans to your serial number. Then finish with Steps 9 and 10: check the cooling unit for leaks and have a technician reset the switch.
STEP 8
Check the fan switch
The fan thermostatic switch turns the fans on when the cooling unit gets hot. Test that it closes when heated.
Is the fan switch okay?
Replace the fan thermostat
Replace the fan thermostatic switch. Then finish with Steps 9 and 10: check the cooling unit for leaks and have a technician reset the switch.
Suspect the cooling unit
The burner, venting and fans all check out, so the cooling unit itself may be overheating. Go to Step 9 to check it for leaks.
LAST · BEFORE ANY RESET
Rule out a cooling unit leak, then have a technician reset the switch.
STEP 9
Inspect the cooling unit for leaks
With the fridge off and cooled down, look over the cooling unit through the lower and upper vents: the boiler, the absorber coils and the area under the fridge. Look for yellow, powdery residue (leaking sodium chromate) and smell for ammonia.
Do you see yellow residue or smell ammonia?
Replace the cooling unit
Those are signs of a leak. The cooling unit is sealed and can’t be repaired. Don’t reset the switch or run the fridge. Replace the cooling unit.
Nordic Cooling Unit 3361A →Replaces 632307. Fits the N641.
Nordic Cooling Unit 3381A →Replaces 632314. Fits the N841.
Norcold Cooling Unit 632316 →Fits all N1095 models.STEP 10
Reset the switch: have a technician do it
Only after every step above checks out, or the cause has been found and fixed. The switch has to be reset to get the fridge running again, but resetting it is a fire risk if the cause of the overheating wasn’t found.
We recommend a certified RV technician
Have a certified RV technician reset the high temperature limit switch and test the fridge after it’s turned back on, on both AC and LP. If the code comes back, turn the fridge off and don’t use it until the cause is found. Need help? Ask a tech.
Still stuck? ask a tech with your model, serial number and the readings you got. We’ll confirm the part before you order.