Norcold N8DC and N10DC 5 Flashes: Power Module Overheating
5 FLASHES
Norcold N8DC and N10DC 5 Flashes: Power Module Overheating
The compressor power module’s circuit board got hotter than 203°F and shut the compressor off. It won’t restart until the board cools below 165°F.
Before you start
- Pull it out first. Most tests need the fridge slid out of its enclosure with 12V still connected.
- Where things are. The compressor, its power module (terminals +, −, F, D, C, P, T), the 15A in-line fuse and the condenser fan are at the back. The touch panel and user interface board are at the top front.
Fits these models
Norcold’s 12V DC compressor refrigerators (8.2 and 9.7 cu ft). These run on 12 volts only: no propane, no 120V heater.
How to read this code
5 flashes, then a pause. This code comes from the compressor power module, not the front panel. You read it with a test LED.
- Pull the fridge out of its enclosure, but keep 12V connected.
- Take the 12V input wire off the module’s + terminal and fit a 1/4″ piggyback adapter on that terminal.
- Connect a 10 mA LED: red lead to the adapter, black lead to terminal D.
- Plug the 12V wire onto the adapter’s other tab. Count the flashes (each is 1/4 second), then the pause, then it repeats.
Write down every code, then remove the LED and adapter. Don’t leave them in for normal use.
STEP 1
Fix what’s trapping heat
Check that the upper and lower vents aren’t blocked, the condenser coil is clean, and it’s under 110°F inside the RV. Leave the fridge OFF until the module cools down.
STEP 2
Restart and watch the fan
Turn the fridge back ON. Make sure the condenser fan at the back is running.
Does the 5-flash code come back?
Repair complete
The fridge is running normally again.
Replace the compressor power module
It’s overheating even with good airflow. It’s the small module bolted to the compressor at the back of the fridge. See the N8DC or N10DC parts or ask a tech.
Still stuck? ask a tech with your model, serial number and the code or readings you got. We’ll confirm the part before you order.
Covers the Norcold N8DC, N8DCX, N10DC and N10DCX. Based on the Norcold N8DCX/N10DCX service manual (640083D), Test E: compressor power module thermal cut-out.